Benha University

Abdel-Salam Hafez Abdel-Salam Hamza

Prof. Emeritus

Faculty of Engineering, Shoubra Electrical Engineering

A proposed transient recovery voltage mitigation technique for generatorcircuit- breaker fed faults

J. Electrical Systems , Journal of Electrical Systems • 2013
Back
Publication Information
Authors Ebrahim A. Badran1, M. A. Abd-Allah, Abdelsalam H. Hamza, Tamer Elyan
Keywords Keywords: GenCB, TRV, RRRV, Fed Faults, ATP-EMTP.
Journal J. Electrical Systems , Journal of Electrical Systems
Publisher J. Electrical Systems
Volume J. Electrical Systems 9-1 (2013
Issue Not Available
Pages 66-72
publication.type International
Paper Link Not Available
Supplementary Materials Not Available
Abstract
In this paper, the generator-circuit-breaker (GenCB) is simulated using ATP-EMTP. The four
main stages of the breaker’s operating processes are considered, namely; the closed contacts
stage, the arc burning stage, the arc extinguishing stage and the opened contacts stage.
Therefore, not only the dynamic conductance during current zero are considered but also the
effects of arc voltage on the arcing times are included. The simulation is tested in a
representative network and the results are compared with IEEE Generator Circuit Breaker
standards. Furthermore, a new mitigation technique is introduced to reduce the transient
recovery voltage (TRV) and the rate of rise of re-striking voltage (RRRV) during switching
period. The results show that the proposed technique successfully reduces both the TRV and
RRRV.