The Performance Enhancement of a Water Chiller of Conically Coiled Tube Evaporator
Engineering and Scientific Research Journal • 2019
Publication Information
Authors
H.A. El-Gammal; M.R. Salem; A.A. Abdulaziz; K.M. Elshazly
Keywords
Experimental; Conically coiled tube; Coefficient of performance; Vapour compression refrigeration system; Taper angle; Pitch
Journal
Engineering and Scientific Research Journal
Publisher
Faculty of Engineering at Shoubra, Benha University
Volume
1
Issue
41
Pages
51-62
publication.type
Local
Paper Link
Open Link
Supplementary Materials
Mohamed Reda Aly Abd-Elhamid Salem_70190_1575078915.pdf
Abstract
The present work experimentally investigates the effect of the geometrical parameters of a conically coiled tube in tube (CCTIT) evaporator and its operating conditions on the coefficient of performance (COP) of a vapour compression refrigeration system (VCRS). The CCTIT evaporator is oriented vertically, through which refrigerant R134a flows in its internal tube, while pure water flows in its annulus as heating mediums, in a counter-flow configuration. Twelve CCTIT evaporators with different taper angles (0135) and pitch ratios (0.07770.1311) are constructed. Totally 72 test runs are performed on the twelve evaporators for heating water flow rates from 1.8 to 14 l/min, which are equivalent to Dean number in the evaporator annulus from 119.8 to 756.4. The experimental results demonstrate that increasing the taper angles and the pitch ratio of the CCTIT evaporator in addition to decreasing the De_(ev,w) augments both the COP of the VCRS. Finally, an experimental correlation is developed to predict the COP of the VCRS as a function of the investigated parameters.